
Reflective Wave Filter, 400/480VAC, 250A
Item #: 958473
Cat #: 1321-RWR250-DP
UPC: 820919873744
Overview
The inverter section of a drive does not produce sinusoidal voltage, but rather a series of voltage pulses created from the DC bus. These pulses travel down the motor cables to the motor and then reflected back to the drive. The reflection is dependant on the rise time of the drive output voltage, cable characteristics, cable length and motor impedance. If the voltage reflection is combined with another subsequent pulse, peak voltages can be at a destructive level. A single IGBT drive output may have reflected wave transient voltage stresses of up to twice (2 pu or per unit) the DC bus voltage between its own output wires. Multiple drive output wires in a single conduit or wire tray further increase output wire voltage stress between multi-drive output wires that are touching. Drive #1 may have a (+) 2 pu stress while drive #2 may simultaneously have a (–) 2 pu stress.
Specifications
| Amps: | 250 |
| Volts AC: | 480, 400 |
| Type: | Reflective Wave Reduction |
| Amps: | 250 |
| Type: | Reflective Wave Reduction |
| Volts AC: | 480, 400 |